Project

General

Profile

Issues #6518

Functional constraint object non-volatility ambiguous - TISSUE 1822

Added by IEC 61850 TPWG 3 months ago. Updated 4 days ago.

Status:
In Progress
Priority:
Normal
Due date:
12/12/2023 (Due in 10 days)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sSrv16 (new)
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Test procedure needs to add steps to consider writable CF, SP, DC.

Write CF/SP/DC, restart device, validate online changes are kept.


Files

Solution to redmine 6518 sSrv16.docx Solution to redmine 6518 sSrv16.docx 21.6 KB Richard Schimmel, 11/14/2023 09:19 AM
#1

Updated by IEC 61850 TPWG 2 months ago

  • Due date changed from 10/03/2023 to 10/17/2023
#2

Updated by IEC 61850 TPWG about 1 month ago

  • Due date changed from 10/17/2023 to 11/14/2023
#3

Updated by Richard Schimmel 18 days ago

  • Initial Test Document set to Ed2.1 TP1.2
  • Test Case ID set to sSrv16 (new)

I propose to add a new (conditional) test case (sSrv16) in the server group.

Test description
1. Client requests SetDataValues of a writable attribute with FC=SP, DC, EX with a new value which is different from the initial value in SCL
2. Client requests GetDataValues
3. Cause DUT restart by simulating a temporarily power outage and client requests associate
4. Client requests GetDataValues

Expected result
1. DUT sends response+
2. DUT sends response+ with the new value
3. DUT send Associate response+
4. DUT sends response+ with the new value

#4

Updated by IEC 61850 TPWG 18 days ago

  • Due date changed from 11/14/2023 to 11/28/2023

Accepted.

#6

Updated by IEC 61850 TPWG 4 days ago

  • Due date changed from 11/28/2023 to 12/12/2023

Add: test one of each FC, selected by the test engineer.