Issues #6473
Inconsistency in LPHD requirements - Tissue 1752
Due date:
10/17/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Files
Updated by IEC 61850 TPWG about 1 year ago
- Subject changed from Inconsistency in LPHD requirements to Inconsistency in LPHD requirements - Tissue 1752
Needs clarification.
Updated by Joel Greene about 1 year ago
- Due date set to 09/05/2023
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Multiple LPHD which are not proxy must have consistent data. Particularly Sim.st
Updated by IEC 61850 TPWG about 1 year ago
Richard to draft new test procedure to validate that data that exists in multiple non-proxy LPHD have consistent values.
Updated by Richard Schimmel about 1 year ago
- File Solution to redmine 6473 LPHD.docx Solution to redmine 6473 LPHD.docx added
- Initial Test Document set to Ed2.1 TP1.2
New test case attached
Updated by IEC 61850 TPWG about 1 year ago
- Due date changed from 10/03/2023 to 10/17/2023
- Status changed from In Progress to Resolved
Updated by Richard Schimmel 7 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3