cSrv7, cSvrN3 some clients only read DA (not DO)

Added by Richard Schimmel over 1 year ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Due date:
07/25/2023 (about 17 months late)
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
cSrv7, cSrvN3
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

These test cases require to test both reading a DA and a DO. Some clients only read a DA. As such we can't test the DO steps.
I propose to add "when supported" to the DO steps.


Files

#1

Updated by IEC 61850 TPWG over 1 year ago

  • Subject changed from cSrv7, sSvrN3 some clients only read DA (not DO) to cSrv7, cSvrN3 some clients only read DA (not DO)
  • Due date set to 07/25/2023
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

Accepted. Richard to modify TP "when supported" to allow device that supports only DA or DO.

#2

Updated by Richard Schimmel over 1 year ago

Attached the solution. Either DA or DO is allowed.

#3

Updated by IEC 61850 TPWG over 1 year ago

  • Status changed from In Progress to Resolved