Project

General

Profile

Issues #642

Blocked/Test-blocked does not impact CSWI->XCBR interface - Tissue Ready to Be Tested

Added by Herbert Falk about 3 years ago. Updated over 2 years ago.

Status:
Closed
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
20, Figures 40-4
61850 Standard:
7-2
Final Decision:
Remove sCtl29
Updated Test Document:
Test Case ID:
sCtl29
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

The state "Operate" in the state machines indicates that OpOpn and OpCls are Set (entry) Reset (exit) while the state "MirrorCBlockedCommand" does not.
The only difference impacted by the Beh beeing blocked / test-blocked, vs beeing on /test is : Activate Output (entry), Desactivate Ouput (exit).
Therefore, even in the state "MirrorBlockedCommand", the CSWI.OpOpn and CSWI.OpCls are set and reset.


Files

Tissue1696_sCtl29 updated.docx Tissue1696_sCtl29 updated.docx 22.9 KB Richard Schimmel, 02/22/2021 08:20 AM

Also available in: Atom PDF