IEC61850-7-5 #6383

Single phase and multi phase trip indication for the autorecloser

Added by Vladan Cvejic 11 months ago.

Status:
New
Priority:
Normal
Assignee:
-
Start date:
03/09/2021
Due date:
09/09/2021 (over 2 years late)
% Done:

0%

Source:
Category:
Not yet categorized
TF 7-5 Project document:
Related TISSUE:

Description

Autorecloser function needs to know if the trip is single-phase or three-phase,
and different actions are taken.
"general" DA means any trip, and "phsX" is activated per-phase, so how to know when
there is a multi-phase or single-phase indication?
The autorecloser function is not able to define, based on the protection and trip
signals, if the fault is single or multiphase. The autorecloser function needs a
specific activation of the single phase or multiphase sequence.


Files

Usecase RREC v0.2.pdf View Usecase RREC v0.2.pdf 249 KB Issue explanation from ELIA Carlos Rodriguez del Castillo, 04/12/2021 09:54 AM

Related issues

Related to IEC 61850 User Feedback Task Force - Support #6605: Identification of three phase trip with ACT DOResolved11/21/2023

Actions
Copied from IEC 61850 User Feedback Task Force - Support #647: Single phase and multi phase trip indication for the autorecloserResolvedCarlos Rodriguez del Castillo03/09/202109/09/2021

Actions