Project

General

Profile

CIM Issues #6282

Update of the 302 and 457 inconsistencies and gaps

Added by Chavdar Ivanov over 1 year ago. Updated about 1 year ago.

Status:
Closed
Priority:
High
Author/Contact Info:
Chavdar Ivanov
Base Release:
CIM17
Solution to be Applied To:
CIM18v04
Solution Version:
CIM18v04
Solution Applied By:
Chavdar Ivanov
Completion Date:
03/04/2023
CIM Keywords:
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):

61970-302, 61970-457

Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
Origination ID:
Originally Assigned To:

Description

Interoperability testing found the following inconsistencies and gaps and proposed these to be fixed asap. The fixes are applied in Ed2 of the standards as they will be voted again due to the copiright changes.

Classes that have attributes as strings, but should be multiple attributes
TurbCIGREHRSGST: pgtqg, pred
TurbIEEEGenericHRSGST: pgtqg, pred
TurbIEEEHydroWCNonlinear: gpm

GovSteamFV4: the block diagram indicates the presence of a deadband in the speed error power reference correction, but no attribute to the purpose is listed

ExcIEEEAC8B: a parameter “Kp” is shown in IEEE specs and missing from attributes list

ExcIEEEST6B: the signal “VB” in IEEE specs is a voltage dependent function (likely analogous to the “KpVt” of IEEEAC8B). Missing from attributes list.

OverexcLimIEEEOEL2C, OverexcLimIEEEOEL3C, OverexcLimIEEEOEL5C: IEEE specs indicate an input selector. Such selector is not in the attributes list.


Proposed Solution

GovCIGREGT and GovIEEEGT1
change type and descroption of attribute fx - boolean
add a1 to a5 attributes, temperature and initialTemperature, pmax

For TurbCIGREHRSGST and TurbIEEEGenericHRSGST: add 6 points pgt and qg. Attribute pdtqg is deleted
add 6 pairs (f1-f6, y1-y6) to represent the output of the block over frequency/under frequency control
delete pred attribute

TurbIEEEHydroWCNonLinear
deleted attribute gpm
added 6 pairs of attributes g1-g6, pm1-pm6

ExcIEEEAC8B
added the statement "However this model is not supporting this, hence the model AC8C from IEEE 421.5-2016, 7.17 (ExcIEEEAC8C) should be used."

ExcIEEEST6B
added the statement "This model is not supporting Vb signal in a correct way, hence the model ST6C from IEEE 421.5-2016, 8.13 (ExcIEEEST6C) should be used."

OverexcLimIEEEOEL2C, OverexcLimIEEEOEL3C, OverexcLimIEEEOEL5C
added attribute inputSignalKind and enumeration OverExcitationLimiterInputKind

GovSteamFV4
Update the diagram of GovSteamFV4 to include parameter Sf1
add the foollowing note to the diagram
"The characteristic using Kf1, Sf1 and alpha has the following details:
Ecf = 1 – Omega
If abs(Ecf) < Sf1 :
Cpfc = 0
else:
Cpfc = Kf1 * (abs(Ecf) – Sf1)
If Cpfc > Lps
Cpfc = Lps
If Cpfc < Lpi
Cpfc = Lpi
where Kf1 is the slope of the characteristic; Alpha is the angle of the slope used only for diagram explanation and the deadband is Sf1."

added attribute sf1


Release Notes

All changes below are applied in 61970-302 and 61970-457

GovCIGREGT and GovIEEEGT1
change type and descroption of attribute fx - boolean
add a1 to a5 attributes, temperature and initialTemperature, pmax

For TurbCIGREHRSGST and TurbIEEEGenericHRSGST: add 6 points pgt and qg. Attribute pdtqg is deleted
add 6 pairs (f1-f6, y1-y6) to represent the output of the block over frequency/under frequency control
delete pred attribute

TurbIEEEHydroWCNonLinear
deleted attribute gpm
added 6 pairs of attributes g1-g6, pm1-pm6

ExcIEEEAC8B
added the statement "However this model is not supporting this, hence the model AC8C from IEEE 421.5-2016, 7.17 (ExcIEEEAC8C) should be used."

ExcIEEEST6B
added the statement "This model is not supporting Vb signal in a correct way, hence the model ST6C from IEEE 421.5-2016, 8.13 (ExcIEEEST6C) should be used."

OverexcLimIEEEOEL2C, OverexcLimIEEEOEL3C, OverexcLimIEEEOEL5C
added attribute inputSignalKind and enumeration OverExcitationLimiterInputKind

GovSteamFV4
Update the diagram of GovSteamFV4 to include parameter Sf1
add the foollowing note to the diagram
"The characteristic using Kf1, Sf1 and alpha has the following details:
Ecf = 1 – Omega
If abs(Ecf) < Sf1 :
Cpfc = 0
else:
Cpfc = Kf1 * (abs(Ecf) – Sf1)
If Cpfc > Lps
Cpfc = Lps
If Cpfc < Lpi
Cpfc = Lpi
where Kf1 is the slope of the characteristic; Alpha is the angle of the slope used only for diagram explanation and the deadband is Sf1."

added attribute sf1

Also available in: Atom PDF