GovCIGREGT and GovCIGREGT1
change type and descroption of attribute fx - boolean
add a1 to a5 attributes, temperature and initialTemperature, pmax
For TurbCIGREHRSGST and TurbIEEEGenericHRSGST: add 6 points pgt and qg. Attribute pdtqg is deleted
add 6 pairs (f1-f6, y1-y6) to represent the output of the block over frequency/under frequency control
delete pred attribute
TurbIEEEHydroWCNonLinear
deleted attribute gpm
added 6 pairs of attributes g1-g6, pm1-pm6
ExcIEEEAC8B
added the statement "However this model is not supporting this, hence the model AC8C from IEEE 421.5-2016, 7.17 (ExcIEEEAC8C) should be used."
ExcIEEEST6B
added the statement "This model is not supporting Vb signal in a correct way, hence the model ST6C from IEEE 421.5-2016, 8.13 (ExcIEEEST6C) should be used."
OverexcLimIEEEOEL2C, OverexcLimIEEEOEL3C, OverexcLimIEEEOEL5C
added attribute inputSignalKind and enumeration OverExcitationLimiterInputKind