GovCIGREGT and GovCIGREGT1 
 change type and descroption of attribute fx - boolean 
 add a1 to a5 attributes, temperature and initialTemperature, pmax 

 For TurbCIGREHRSGST and TurbIEEEGenericHRSGST: add 6 points pgt and qg. Attribute pdtqg is deleted  
 add 6 pairs (f1-f6, y1-y6) to represent the output of    the block over frequency/under frequency control 
 delete pred attribute 

 TurbIEEEHydroWCNonLinear 
 deleted attribute gpm 
 added 6 pairs of attributes g1-g6, pm1-pm6 


 ExcIEEEAC8B 
 added the statement "However this model is not supporting this, hence the model AC8C from IEEE 421.5-2016, 7.17 (ExcIEEEAC8C) should be used." 

 ExcIEEEST6B 
 added the statement "This model is not supporting Vb signal in a correct way, hence the model ST6C from IEEE 421.5-2016, 8.13 (ExcIEEEST6C) should be used." 

 OverexcLimIEEEOEL2C, OverexcLimIEEEOEL3C, OverexcLimIEEEOEL5C 
 added attribute inputSignalKind and enumeration OverExcitationLimiterInputKind