Improvement #626
Extension of P-type to describe connexion type (PhysCon)
Added by Carlos Rodriguez del Castillo almost 4 years ago.
Updated 12 months ago.
Category:
Standard extension required
Due date:
05/24/2021 (over 3 years late)
Discuss in Upcoming Meeting:
No
Short Proposal:
Extent the P-type to include new standardized types. See notes.
Standard(s):
TR IEC 61850-90-4, IEC 61850-6
Needs More Information:
No
Assigned TF:
61850-6, 61850-90-4 (LAN Network Engineering)
Description
We propose to add, for P Type = Type, the values : 1000BaseT, 100BaseFX, 1000BaseLX, monomode, and for P type = Plug, the value : LC.
Standardized useful types.
- Status changed from New to In Progress
- Short Proposal set to Extent the P-type to include new standardized types. See notes.
Extent the P-type to include new standardized types. Take into into account in edition 3 of part 6 to create a pre-defined list to be used by users. The current list is a recomendation. We have to create a tissue for that.
Another issue is to create service communication capability for the port identifiying which services are available in each port (GOOSE, MMS, only GOOSE, GOOSE+MMS, NTP):
- MMS is available if IP address is defined
- GOOSE and SV are available in <Services>
Decision: Services in the access point describe the capabilities and there is no need to duplicate the information in P-type in communication section.
- Due date set to 05/24/2021
- Assignee set to Camille Bloch
- Discuss in Upcoming Meeting changed from Yes to No
- To discuss in WG10 set to No
2021-03-02: Camille will create the tissue and maybe it could be included in amendment 2.2 since it is not impacting existing configuration
- Discuss in Upcoming Meeting changed from No to Yes
- Needs More Information set to Yes
- Status changed from In Progress to Resolved
- Discuss in Upcoming Meeting changed from Yes to No
- Standard(s) changed from IEC 61850-6 to TR IEC 61850-90-4, IEC 61850-6
- Needs More Information changed from Yes to No
- Assigned TF 61850-6, 61850-90-4 (LAN Network Engineering) added
To the Editor of Part 90-4:
recommendation to update the list of Type and Plug in new version of document. That will be the entry for change in Part 6.
To the Editor of Part 6:
recommendation to introduce Enum for Type and Plug with new entries (as suggested in this issue).
Also available in: Atom
PDF