Project

General

Profile

Issues #6227

sDoc5 GSESettings/SMVsettings apply for SendGOOSE/SMVmessage not SetGoCBValues/SetMsvCBValues

Added by Richard Schimmel almost 2 years ago. Updated 9 months ago.

Status:
Closed
Priority:
Normal
Due date:
02/07/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
6
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

GSESettings is related to "S39" SetGoCBValues, but we also need to know if the dataset is configurable or fixed. I propose to change the condition to "S35 publisher" SendGOOSEmessage

Same for SMVSettings from S47||S50 to S45 SendSMVmessage

#1

Updated by IEC 61850 TPWG almost 2 years ago

  • Due date set to 02/07/2023
  • Status changed from New to Resolved
  • Assignee set to Richard Schimmel

Accepted.

#2

Updated by Richard Schimmel 9 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3

Also available in: Atom PDF