Project

General

Profile

Feature #6224

Parameters not available in standardized GAPC LN - SetRef

Added by Carlos Rodriguez del Castillo almost 2 years ago. Updated almost 2 years ago.

Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
Standard extension required
Start date:
11/24/2020
Due date:
05/24/2021 (over 3 years late)
% Done:

0%

Estimated time:
ID:
59
Source:
RTE
TF Unique ID:
59 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4

Needs More Information:
Yes
Assigned TF:

Description

SetRef: Setting for indicating an IEC 61850 object reference. Some function need to have a setting indicating which input (for example SV streams, phasors, CB position…) has to be used.
There is no setting DO defined in existing LN, it is proposed to add this DO in LN GAPC to make it generic.

More details on use cases (see attached documents):
  • Use case 1: recloser function where it is necessary to use the line voltage and busbar voltage. The busbar voltage to be used depends on the topology of the substation. This means that an external function needs to indicate which voltage busbar is to be used. The SetRef is written by the external function and corresponds to the TVTR stream of the relevant merging unit. It cannot be done by configuration as the topology changes dynamically depending on the state of circuit breaker and disconnector switches.
  • Use case 2: in case of redundant SV streams, several merging unit may be eligible to provide the SV stream use for the function.

Since the opening of the issue, RTE has chosen to use InRef and dynamically write the SrcCBRef (with an external function) to cover these use cases. No other uses cases that could not be covered this way have been identified. There is no longer need to have implementation of SetRef.

[New parametres need to be modelled in GAPC LN. This issue refer to SetRef parameters, as explained in the attached documents by RTE.]


Files

20210326-RTE Use cases 622.docx 20210326-RTE Use cases 622.docx 20.2 KB Use case explanation Carlos Rodriguez del Castillo, 05/25/2021 10:14 AM
20210326-RTE Use cases 622_v2.docx 20210326-RTE Use cases 622_v2.docx 24 KB more details on use cases Maud Merley, 12/04/2022 11:56 PM

Related issues

Copied from IEC 61850 User Feedback Task Force - Feature #6223: Parameters not available in standardized GAPC LN - StrValIn Progress11/24/202005/24/2021

Actions
#1

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Copied from Feature #6223: Parameters not available in standardized GAPC LN - StrVal added
#2

Updated by Carlos Rodriguez del Castillo almost 2 years ago

  • Description updated (diff)
#3

Updated by Vladan Cvejic almost 2 years ago

  • Status changed from New to In Progress
#4

Updated by Vladan Cvejic almost 2 years ago

It is concluded that issue has to be presented and discussed on next joint meeting of TC57 & TC38 & TC95 in Lyon (May 25th, 2023). Will be presented by Maud Merley.

#5

Updated by Vladan Cvejic almost 2 years ago

  • Discuss in Upcoming Meeting changed from Yes to No

Also available in: Atom PDF