WG10 Future Work #6144
Need to add SCL mechanism to define a minimum MinTime
0%
IEC 61850-6
Description
If there is an issue reported, please report the test case number/name that was being executed.
The device (AA1D1Q01BPU2) has a minimum Goose MinTime of 10ms.
The SCD file has a minimum Goose MinTime of 5ms for this device.
The configured device uses the 10ms, as discovered by a client.
The SCL schema has no feature to indicate the minimum MinTime.
Proposal descriptions
Add a feature to SCL to indicate a minimum MinTime.
Need to add a Services Section for a Minimum-MinTime. Physical Device characteristic input from ICD to SCT to tell the SCT the engineering parameters.
SCL is lacking a mechanism to provide/protect information for a predefined control block. For GOOSE Control blocks predefined forward to WG10, propose an attribute for minTime in the Communication section that indicates a minimum-MinTime. Could also go in as an attribute of the GSEControl itself.
Place as a future issue in Redmine.
Updated by Vladan Cvejic over 1 year ago
- Tracker changed from WG10FutureWork to WG10 Future Work
- Source deleted (
IOP 2022) - Discuss in Upcoming Meeting deleted (
No) - Proposal descriptions updated (diff)
Updated by Vladan Cvejic over 1 year ago
- Source set to IOP 2022
- Discuss in Upcoming Meeting set to No
- Proposal descriptions updated (diff)
- Needs More Information set to No
Updated by Vladan Cvejic about 1 year ago
- Standard(s) set to IEC 61850-6
- Target edition changed from Not assigned to Next
- Assigned TF 61850-6 added