WG10 Future Work #6144
Updated by Vladan Cvejic over 1 year ago
Add a feature to SCL to indicate a minimum MinTime. Need to add a Services Section for a Minimum-MinTime. Physical Device characteristic input from ICD to SCT to tell the SCT the engineering parameters. SCL is lacking a mechanism to provide/protect information for a predefined control block. For GOOSE Control blocks predefined forward to WG10, propose an attribute for minTime in the Communication section that indicates a minimum-MinTime. Could also go in as an attribute of the GSEControl itself. Place as a future issue in Redmine.