Project

General

Profile

Issues #6142

TemplatePics_Ed1Ed2Ed2p1_Excel_rev3p1 contains wrong comment for T2

Added by christian zehnder about 2 years ago. Updated over 1 year ago.

Status:
Closed
Priority:
Normal
Assignee:
Due date:
03/07/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

Assume its a typo in the latest PICS template on ACSI Service tab for T2:
T3 (µs) (<= 25 µs), 15 <= T3 < 18
T4 (µs) (<= 25 µs), 18 <= T3 < 19

According 7-2:2010 and 2020 T4 is 4us not 25:

T4 (µs) (<= 4 µs), 18 <= T3 < 19