Issues #6142
TemplatePics_Ed1Ed2Ed2p1_Excel_rev3p1 contains wrong comment for T2
Due date:
03/07/2023
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
Assume its a typo in the latest PICS template on ACSI Service tab for T2:
T3 (µs) (<= 25 µs), 15 <= T3 < 18
T4 (µs) (<= 25 µs), 18 <= T3 < 19
According 7-2:2010 and 2020 T4 is 4us not 25:
T4 (µs) (<= 4 µs), 18 <= T3 < 19
Updated by IEC 61850 TPWG about 2 years ago
- Due date set to 10/18/2022
- Status changed from New to In Progress
- Assignee set to Joel Greene
Agreed, typo to be fixed.
Updated by IEC 61850 TPWG about 2 years ago
- Due date changed from 10/18/2022 to 11/01/2022
PICS template to be updated.
Updated by IEC 61850 TPWG almost 2 years ago
- Due date changed from 01/24/2023 to 02/07/2023
TemplatePics_Ed1Ed2Ed2p1_Excel_rev3p0 has been uploaded to the SharePoint. Please verify if this resolves the issue.
TemplatePics_Ed1Ed2Ed2p1_Excel_rev3p1 has not been located.
Updated by IEC 61850 TPWG almost 2 years ago
- Status changed from In Progress to Closed
updated template posted.