Project

General

Profile

Feature #602

Merging Unit standard requires MU clock to jump on PTP time jumps, which is not true for Boundary Clocks.

Added by Herbert Falk almost 4 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
-
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1742
Source:
IOP_2019
TF Unique ID:
1742 # IOP_2019
WG10 Proposal:

TISSUE needs to be raised against 61850-9-3 to place requirements on Boundary clocksFeb-20: CRC: Check with Huber (put Christoph Brunner in copy of the e-mail)Jun-20: CRC: Check the answer from Hubert and also wait to see if 9-3 is going to be reviewed

Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Involves step requirement of 61869-9. With boundary clocks that ramp, IEDs will not be able to meet the step requirement of 61869-9

Standard(s):

IEC 61850-9-3

Needs More Information:
No
Assigned TF:

Description

Merging Unit standard requires MU clock to jump on PTP time jumps. But this cannot work if Boundary clocks exist between the clock source and sink because boundary clocks are not required to perform this jump.
Improvements are needed.