Issues #5958
sTm2 allow a more accurate Time Accuracy as documented
Due date:
09/20/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sTm2
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sTm2 step 3 expected result requires that the device TimeAccuracy "matches" with the documented resolution PICS-T2.
Some devices have a dynamic time accuracy which can be even higher/better as the documented PICS-T2. For example the PICS-T2 is 10 bits and the device reports 11 bits accuracy. Such device should pass the test.
Propose to add "at least" in:
3. the TimeStamp - TimeQuality - TimeAccuracy at least matches the documented resolution (PICS-T2)
Updated by IEC 61850 TPWG about 2 years ago
- Due date set to 09/20/2022
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3