Project

General

Profile

WG10 Future Work #5937

Report of current active setting group

Added by Vladan Cvejic over 1 year ago. Updated 2 months ago.

Status:
New
Priority:
Normal
Assignee:
-
Start date:
05/11/2021
Due date:
% Done:

0%

Estimated time:
Source:
WG10
TF Unique ID:
WG10 # 4
WG10 Proposal:
Discuss in Upcoming Meeting:
No
Short Proposal:

To create a new INS data object in the LLN0 where SCGB is defined. A new presence condition is needed. To be included in IEC 61850-7-4 ed3.

Standard(s):

IEC 61850-7-4

Needs More Information:
No
Assigned TF:
61850-7-4
Target edition:
Next

Description

The current active setting group cannot be sent in a report in an spontaneous way, and you can only use GetDataValues (polling) service.
Today some users define a INS data object with the setting group number, others define several SPS objects to indicate which seeting group is active.


Proposal descriptions

Service tracking gives information about the current setting group, but it is not possible by GOOSE or report. If you want to raise an action on other device due to a setting group change, then you need a data object with TrgOpts d-chg in order to be able to do it.


Related issues

Copied from IEC 61850 User Feedback Task Force - Improvement #667: Report of current active setting groupResolved05/11/202111/11/2021

Actions

Also available in: Atom PDF