WG10 Future Work #5931

CIM-61850 Harmonization - Add string attribute psrType to tPowerSystemResource.

Added by Vladan Cvejic over 2 years ago. Updated 10 months ago.

Status:
New
Priority:
Normal
Assignee:
-
Start date:
07/13/2022
Due date:
% Done:

0%

Estimated time:
Source:
IEC 62361-102 R3
TF Unique ID:
WG10 Proposal:
Discuss in Upcoming Meeting:
No
Short Proposal:
Standard(s):

IEC 61850-6

Needs More Information:
No
Assigned TF:
61850-6
Target edition:
Next

Description

IEC 62361-102 Recommendation R3

5.6.4 Recommendation for harmonization: SCL PSRType

In the CIM, instances of power system resources may be associated with zero or one
instances of PSRType. This is used for “classifying instances of the same class, e.g.
overhead and underground ACLineSegments. This classification mechanism is intended to
provide flexibility outside the scope of this standard, i.e. provide customisation that is nonstandard.”

This custom classification is particularly useful for modelling distribution network equipment,
as a way of defining individual instances with reference to template or catalogue objects that
contain sets of reference parameters.
It would also help mapping algorithms to choose the appropriate CIM class when there is a
choice, e.g. a physical line could be modelled as an ACLineSegment, but for transmission
network applications it could be modelled as an EnergyConsumer (a point of consumption on
the power system model)

Recommendation R3: An optional string attribute psrType should be added to the SCL
definition for tPowerSystemResource. It may be appropriate to use a specific namespace for
this and other CIM related attributes.


Proposal descriptions

Add optional string attribute psrType to the SCL definition for tPowerSystemResource. It may be appropriate to use a specific namespace for this and other CIM related attributes.