IEC 62361-102 R9
TF Unique ID:
WG10 Proposal:
Discuss in Upcoming Meeting:
No
Short Proposal:
Standard(s):
IEC 61850-6
Needs More Information:
No
Assigned TF:
61850-6
Target edition:
Next
Description
IEC 62361-102 Recommendation R9
The SCL enumeration for phases is more restricted than the PhaseCode enumeration defined
in the CIM. It suits the physical equipment found in large substations but is inefficient for
modelling equipment found in distribution networks or consumer premises. At present users
are forced to define sets of Equipment and SubEquipment instances in order to model single
real-world devices.
Proposal descriptions
In IEC 61850-6, extend the existing tPhaseEnum to use the same enumerations as the CIM PhaseCode.