Need to test that IEDs support 1 Step and 2 Step clocks: IOP 2022

Added by Herbert Falk over 1 year ago. Updated 28 days ago.

Status:
Closed
Priority:
Normal
Due date:
10/04/2022
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
9-3
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sTmP1
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

During the 2022 IEC 61850 IOP, it was found that some IEDs would not sync to clocks that are 1 step. This lead to protection being blocked.

A test needs to be added.

An analysis also needs to be done if such a test is needed for a client.


Files

#1

Updated by Herbert Falk over 1 year ago

  • 61850 Standard 9-2, 9-3 added
#2

Updated by IEC 61850 TPWG over 1 year ago

  • Due date set to 10/04/2022
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

Discuss with Jay Anderson and Jean-Sebastian

9-3 in revision.

refer to 1588 until 9-3 is published?

#3

Updated by Richard Schimmel over 1 year ago

Update sTmP1 to repeat the test for 1-step and 2-step

#4

Updated by IEC 61850 TPWG over 1 year ago

  • Status changed from In Progress to Resolved
#5

Updated by Richard Schimmel 28 days ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3