Issues #5906
sCnf51 at least one LPHD
Due date:
09/06/2022 (about 5 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
8.2.5
61850 Standard:
7-1
Triggering Tissue:
Final Decision:
rejected
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
No Action Taken
Triggering Tissue 2:
Triggering Tissue 3:
Description
Part 7-1 clause 8.2.1 states "at least one LPHD" shall be available in a server device.
The sCnf51 test procedure requires:
"LPHD is present in each root logical device"
Propose to change into:
"LPHD is present in at least one root logical device"
and change the clause reference to 8.2.1
Updated by IEC 61850 TPWG 6 months ago
- Due date set to 09/06/2022
- Status changed from New to Resolved
- Assignee set to Richard Schimmel
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)
Update TP to at least one
Updated by Joel Greene 6 months ago
- Status changed from Resolved to In Progress
Hmmm...
"LPHD is present in each root logical device" comes from 8.2.5 which defines root as not having GrRef.
Updated by Richard Schimmel 6 months ago
Indeed part 7-1 clause 8.2.5 is very specific: "LPHD shall be present in any root logical device". Propose to reject/close this issue, no change.
Updated by Richard Schimmel 6 months ago
- Status changed from In Progress to Rejected
- Clause Reference set to 8.2.5
- Final Decision set to rejected
- Test Case ID deleted (
sCnf51) - Closed Reason No Action Taken added
- Closed Reason deleted (
Test Procedure Update)
Rejected, keep sCnf51 as is.