Feature #588
More than one redundant PhysConn for ConnectedAP of IED AP and no redundant PhysConn on same AP
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
1548
Source:
IOP_2019
TF Unique ID:
1548 # IOP_2019
WG10 Proposal:
Part 6 (9.4.6 bullet 3 of restrictions) states that there can be only one (maximum) RedConn if there is a Connection physical port
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Resolve how RedCon are allowed
Standard(s):
IEC 61850-6
Needs More Information:
Assigned TF:
Description
There is more than one redundant PhysConn for ConnectedAP of IED AccessPoint “S1”. In addition there are none redundant PhysConn on same AP.
<PhysConn type="Connection">
<P type="Port">1-A</P>
<P type="Plug">RJ45</P>
<P type="Type">100BaseT</P>
<P type="Cable">1</P>
</PhysConn>
<PhysConn type="RedConn">
<P type="Port">1-B</P>
<P type="Plug">RJ45</P>
<P type="Type">100BaseT</P>
<P type="Cable">2</P>
</PhysConn>
<PhysConn type="RedConn">
<P type="Port">1-C</P>
<P type="Plug">LC</P>
<P type="Type">FOC</P>
<P type="Cable">3</P>
</PhysConn>