Project

General

Profile

Feature #588

More than one redundant PhysConn for ConnectedAP of IED AP and no redundant PhysConn on same AP

Added by Herbert Falk over 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Implementation - improve conformance testing
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
1548
Source:
IOP_2019
TF Unique ID:
1548 # IOP_2019
WG10 Proposal:

Part 6 (9.4.6 bullet 3 of restrictions) states that there can be only one (maximum) RedConn if there is a Connection physical port

Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Resolve how RedCon are allowed

Standard(s):

IEC 61850-6

Needs More Information:
Assigned TF:

Description

There is more than one redundant PhysConn for ConnectedAP of IED AccessPoint “S1”. In addition there are none redundant PhysConn on same AP.
<PhysConn type="Connection">
<P type="Port">1-A</P>
<P type="Plug">RJ45</P>
<P type="Type">100BaseT</P>
<P type="Cable">1</P>
</PhysConn>
<PhysConn type="RedConn">
<P type="Port">1-B</P>
<P type="Plug">RJ45</P>
<P type="Type">100BaseT</P>
<P type="Cable">2</P>
</PhysConn>
<PhysConn type="RedConn">
<P type="Port">1-C</P>
<P type="Plug">LC</P>
<P type="Type">FOC</P>
<P type="Cable">3</P>
</PhysConn>

Also available in: Atom PDF