Feature #578
Busbar protection: End Fault protection - model definition required.
0%
To create new LN (name: REFP)(19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C). Possible new LN PSTB
IEC 61850-7-4
Description
Busbar protection: End Fault protection
It is related to dead zone (to protected small section between breaker and CT).
In most cases, bus coupler is not having 2 CTs across the breaker to create overlapping zones and protect dead zone. Thus, with supervision of CB position (if breaker is open) and measuring threshold current of respective CT, BBP can be triggered to clear the fault in dead zone (solution depends on position of CT relative to protective zone).
In existing vendor solutions today, extension of modeling is used to create REFP (protection related function End Fault Protection). It should be defined in IEC 61850 model.
Updated by Vladan Cvejic about 4 years ago
- Subject changed from Busbar protection: End Fault protection It is related to dead zone (to protected small section between breaker and CT). In most to Busbar protection: End Fault protection - model definition required.
- Short Proposal changed from To create new LN (name: REFP) (19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C). Possible new LN PSTB to To create new LN (name: REFP)(19-06-06) To create Use-case with different scenarios in order to clearly define scope of application (Vladan C). Possible new LN PSTB
- Standard(s) set to IEC 61850-7-4
- Discuss in Upcoming Meeting set to No
Checking done.
Updated by Vladan Cvejic over 2 years ago
- Status changed from In Progress to Closed
- To discuss in WG10 set to No
- Needs More Information set to Yes
Since there is no representation from ENTSO-E anymore we can close these tickets for now. Additionally, we can eventually re-open if in the future similar needs are identified by other users.