Project

General

Profile

Support #553

IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable

Added by Herbert Falk about 3 years ago. Updated 11 months ago.

Status:
Resolved
Priority:
Normal
Category:
Standard clarification required
Start date:
Due date:
% Done:

0%

Estimated time:
ID:
34
Source:
IOP_2017/55
TF Unique ID:
34 # IOP_2017/55
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:

To send to Hubert for next 9-3 revision

Standard(s):

IEC 61850-9-3

Needs More Information:
No
Assigned TF:

Description

IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable.
In particular, it should clarify that the clockAccuracy is only valid if TimeTraceable is true, and that
a temporary loss of signal to the reference clock does not clear the TimeTraceable flag, as long as the master retains the ability to announce a leap second correctly.


Proposal descriptions

Assigned to IEC 61850-9-3