Support #553
IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
34
Source:
IOP_2017/55
TF Unique ID:
34 # IOP_2017/55
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
To send to Hubert for next 9-3 revision
Standard(s):
IEC 61850-9-3
Needs More Information:
No
Assigned TF:
Description
IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable.
In particular, it should clarify that the clockAccuracy is only valid if TimeTraceable is true, and that
a temporary loss of signal to the reference clock does not clear the TimeTraceable flag, as long as the master retains the ability to announce a leap second correctly.
Proposal descriptions
Assigned to IEC 61850-9-3
Updated by Vladan Cvejic almost 4 years ago
- Subject changed from IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable. In particular, it should clarify to IEC/IEEE 61850-9-3 should clarify the meaning and use of TimeTraceable and FrequencyTraceable
- Category set to Standard clarification required
- Status changed from New to In Progress
- Standard(s) changed from 3-Sep to IEC 61850-9-3
- Discuss in Upcoming Meeting set to No
Checking done.
Updated by Carlos Rodriguez del Castillo over 2 years ago
- Status changed from In Progress to Resolved
- Assignee set to Fred Steinhauser
- Proposal descriptions updated (diff)