Support #552
Disruption of network when TC are not set to the correct domain
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
33
Source:
IOP_2017/54
TF Unique ID:
33 # IOP_2017/54
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
To send to Hubert for next 9-3 revision
Standard(s):
IEC 61850-9-3
Needs More Information:
No
Assigned TF:
Description
Some TC that are not set to the correct domain disrupt the network because they do not respond to
Pdelay_Req coming from another domain than their own.
This means that a replacement TC inserted out of the box could disrupt the network until it is properly configured.
According to IEEE 1588:2008, a TC only has a “primary domain” for syntonization, but otherwise should respond to other domain TCs should respond to other domains.
A slave-only clock is not obliged to respond to a Pdelay_Req that is not from its domain.
To be clarified in IEC/IEEE 61850-9-3.
Proposal descriptions
Assigned to IEC 61850-9-3