Description

Both classes' .grounded attributes say "Used for Yn and Zn connections. True if the neutral is solidly grounded.” In both cases the attribute describing connection (ShuntCompensator.phaseConnection and EnergyConsumer.phaseConnection respectively) are of datatype PhaseShuntConnectionKind whose possible values are: D, Y, Yn, I, G. It is not possible to specify a "Zn" connection.


Proposed Solution

Suggest changing the .grounded attribute descriptions to say:
ShuntCompensator.grounded “Required for Yn and I connections (as represented by ShuntCompensator.phaseConnection). True if the neutral is solidly grounded.”
EnergyConsumer.grounded “Required for Yn and I connections (as represented by EnergyConsumer.phaseConnection). True if the neutral is solidly grounded.”


Decision

09-May-2022 WG13 agrees with the changes


Release Notes

The descriptions are changed as follows
ShuntCompensator.grounded “Required for Yn and I connections (as represented by ShuntCompensator.phaseConnection). True if the neutral is solidly grounded.”
EnergyConsumer.grounded “Required for Yn and I connections (as represented by EnergyConsumer.phaseConnection). True if the neutral is solidly grounded.”

#1

Updated by Yang Feng almost 2 years ago

  • Decision updated (diff)
#2

Updated by Yang Feng over 1 year ago

  • Solution to be Applied To set to CIM18v03
#3

Updated by Chavdar Ivanov over 1 year ago

Hi Yang, Eric,
Can you change the status of this issue to In Progress as it is decided?

#4

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from New to Open
  • Solution Version set to CIM18v03
  • Solution Applied By set to Chavdar Ivanov
  • Completion Date set to 02/07/2023
  • Release Notes updated (diff)
#5

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from Open to In Progress
#6

Updated by Chavdar Ivanov about 1 year ago

  • Status changed from In Progress to Closed

Also available in: Atom PDF