Documentation on ShuntCompensator.grounded and EnergyConsumer.grounded attributes
61970-301, 61970-452
Description
Both classes' .grounded attributes say "Used for Yn and Zn connections. True if the neutral is solidly grounded.” In both cases the attribute describing connection (ShuntCompensator.phaseConnection and EnergyConsumer.phaseConnection respectively) are of datatype PhaseShuntConnectionKind whose possible values are: D, Y, Yn, I, G. It is not possible to specify a "Zn" connection.
Proposed Solution
Suggest changing the .grounded attribute descriptions to say:
ShuntCompensator.grounded “Required for Yn and I connections (as represented by ShuntCompensator.phaseConnection). True if the neutral is solidly grounded.”
EnergyConsumer.grounded “Required for Yn and I connections (as represented by EnergyConsumer.phaseConnection). True if the neutral is solidly grounded.”
Decision
09-May-2022 WG13 agrees with the changes
Release Notes
The descriptions are changed as follows
ShuntCompensator.grounded “Required for Yn and I connections (as represented by ShuntCompensator.phaseConnection). True if the neutral is solidly grounded.”
EnergyConsumer.grounded “Required for Yn and I connections (as represented by EnergyConsumer.phaseConnection). True if the neutral is solidly grounded.”
Updated by Chavdar Ivanov about 2 years ago
Hi Yang, Eric,
Can you change the status of this issue to In Progress as it is decided?
Updated by Chavdar Ivanov almost 2 years ago
- Status changed from New to Open
- Solution Version set to CIM18v03
- Solution Applied By set to Chavdar Ivanov
- Completion Date set to 02/07/2023
- Release Notes updated (diff)