Issues #5344
sBr29 power-up the IED is missing
Status:
Rejected
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sBr29
Closed Reason:
No Action Taken
Triggering Tissue 2:
Triggering Tissue 3:
Description
The test procedure does not perform a restart of the DUT. It's referring to PIXIT As8 restart time.
We propose to update the test description as follows:
Step 1: configure the device with a BRCB with a valid dataset and trigger option data change or
integrity
Step 2: restart DUT and wait until the time specified in PIXIT As8.
Step 3: generate data change or wait for integrity report
Step 4: reserve and enable BRCB without resync
Expected result
step 4: All the reports in step 4 are buffered