Clarifications on the local/remote concept 6/8

Added by Carlos Rodriguez del Castillo over 3 years ago. Updated over 1 year ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
01/20/2022 (over 2 years late)
% Done:

0%

Estimated time:
ID:
10
Source:
MH
TF Unique ID:
10 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850-7-4 Ed2.1 ,7-5

Needs More Information:
No
Assigned TF:

Description

Add a statement in the description text of 'SwModKey' that this setting effects all contained CSWI LN instances of that LD.
Is the dependency of 'SwModKey' limited to contained CSWI LN instances of that LD or, in the case of nested LD, including also subordinate levels?


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
Copied to 61850-7-5 and 61850-7-500 - IEC61850-7-5 #6392: Clarifications on the local/remote concept 6/8In Progress09/20/202101/20/2022

Actions
#1

Updated by Vladan Cvejic almost 3 years ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#2

Updated by Vladan Cvejic almost 3 years ago

  • Status changed from New to In Progress
#3

Updated by Vladan Cvejic almost 3 years ago

  • Status changed from In Progress to Resolved
  • Discuss in Upcoming Meeting changed from Yes to No
#4

Updated by Tom Berry almost 3 years ago

Draft proposal
When there are nested logical devices, the control service checks for SwModKey should be similar to the checks for Mod/Beh.

When a control request is received at a Logical Node, the checks should take into account the status of the SwModKey data object of the logical node, and also the SwModKey data object of the LLN0 for all containing logical devices.
In the case of different values, "SwModKey=false" is dominant i.e. interlocking checks are made

#5

Updated by Carlos Rodriguez del Castillo almost 3 years ago

  • Assignee set to Tom Berry
#6

Updated by Tom Berry almost 3 years ago

  • Standard(s) changed from IEC 61850-7-4 Ed2.1 to IEC 61850-7-4 Ed2.1 ,7-5
#7

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Needs More Information set to No
#8

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
#9

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No
#10

Updated by Vladan Cvejic over 1 year ago

Also available in: Atom PDF