Project

General

Profile

Feature #5085

Clarifications on the local/remote concept 5/8

Added by Carlos Rodriguez del Castillo over 1 year ago. Updated 23 days ago.

Status:
Resolved
Priority:
Normal
Assignee:
Category:
Standard clarification required
Start date:
09/20/2021
Due date:
03/20/2022 (about 15 months late)
% Done:

0%

Estimated time:
ID:
9
Source:
MH
TF Unique ID:
9 # MH
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
Yes
To discuss in WG10:
No
Short Proposal:
Standard(s):

IEC 61850 7-1 / 7-4 Ed2.1,7-5

Needs More Information:
No

Description

Add a statement about the dependency of 'LN.Loc' contained in LD from LD/LLN0.Loc (and LocSta, as applicable). Is this dependency limited to contained LN instances of that LD or, in the case of nested LD, including also subordinate levels? (see Tissue 1778)


Related issues

Related to IEC 61850 User Feedback Task Force - Feature #5081: Clarifications on the local/remote concept 1/8ResolvedTom Berry09/20/2021

Actions
#1

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Due date set to 03/20/2022
  • To discuss in WG10 changed from Yes to No
#2

Updated by Vladan Cvejic over 1 year ago

  • Related to Feature #5081: Clarifications on the local/remote concept 1/8 added
#3

Updated by Vladan Cvejic over 1 year ago

  • Status changed from New to In Progress
#4

Updated by Vladan Cvejic over 1 year ago

  • Status changed from In Progress to Resolved
#5

Updated by Tom Berry over 1 year ago

Draft proposal
When there are nested logical devices, the control service checks for local/remote should be similar to the checks for Mod/Beh.

When a control request is received at a Logical Node, the checks should take into account the status of the Loc, LocSta, MltLev data objects of the logical node, and also the Loc, LocSta, MltLev data objects of the LLN0 for all containing logical devices.
In the case of different values, "Loc=true", "LocSta=true", "MltLev=False" are dominant.

#6

Updated by Carlos Rodriguez del Castillo over 1 year ago

  • Assignee set to Tom Berry
#7

Updated by Tom Berry over 1 year ago

  • Standard(s) changed from IEC 61850 7-1 / 7-4 Ed2.1 to IEC 61850 7-1 / 7-4 Ed2.1,7-5
#8

Updated by Carlos Rodriguez del Castillo 23 days ago

  • Needs More Information set to No
#9

Updated by Carlos Rodriguez del Castillo 23 days ago

  • Discuss in Upcoming Meeting changed from No to Yes

Also available in: Atom PDF