sCnf121 serNum and hwRev values
Description
The sCnf121 test case requires among others that LPHD.PhyName.serNum and hwRev are present and not empty in the SCL file. After a closer look at clause 6.903.5 this clause does not specify if the values are "configured" in the SCL or read via the MMS interface.
Considering the use case that (broken) hardware can be replaced without changing the configuration it make sense that the serNum and hwRev values are not configured in SCL and have non-empty values when read from the IED via MMS.
Proposal is to require the presence of these attributes in SCL and have non-empty values when read via MMS.
6.903.5 Logical nodes LPHD
LPHD logical nodes shall be as specified in IEC 61850-7-4:2010, 5.3.2, except that the LPHD
logical nodes shall be extended by the addition of the nameplate data objects defined in
Table 903. The value of dataNs data attributes of these extended data objects shall be
“IEC 61869-9:2016”. The data attributes of these extended data objects shall be read-only.
The LPHD data object PhyNam shall conform to the DPL common data class definition in
IEC 61850-7-3:2010, 7.8.2, except that attributes PhyNam.vendor, PhyNam.model,
PhyNam.serNum, PhyNam.hwRev, PhyNam.swRev and PhyNam.d are mandatory and readonly.
For attribute PhyNam.serNum, where the manufacturing date is not implicit in the serial
number, the date of manufacture shall be included.
Files
Updated by Joel Greene over 3 years ago
Agree. The attributes must be present in the type templates, but the values for these should not be in SCL.
Updated by Richard Schimmel over 3 years ago
- File Solution to redmine_3103_sCnf121.docx Solution to redmine_3103_sCnf121.docx added
- Status changed from New to In Progress
Attached proposal. Also changed NamAuxVRtg to optional.
Updated by Thierry Dufaure over 3 years ago
I agree with the explanations and modifications from Richard in file redmine_3103_sCnf121.docx
Updated by Gunnar Hilpert over 3 years ago
Same: I agree with the explanations and modifications from Richard in file redmine_3103_sCnf121.docx
Updated by Richard Schimmel about 3 years ago
- File Solution to redmine_3103_sCnf121_20210824.docx Solution to redmine_3103_sCnf121_20210824.docx added
- Test Case ID changed from sCnf121 to sCnf121, sSvp23
TPWG Aug24: move the MMS GetDataValues to a new conditional sSvp23 test case.
After close look in IEC 61869-9 clause 6.903.5 only PhyNam.serNum has a value requirement: For attribute PhyNam.serNum, where the manufacturing date is not implicit in the serial number, the date of manufacture shall be included.
Therefor we can't require a non-empty value for other PhyName attributes.
Updated by Richard Schimmel about 3 years ago
- File Solution to redmine_3103_sCnf121_20210827.docx Solution to redmine_3103_sCnf121_20210827.docx added
After closer look at part 7-3 the PhyNam attributes have certain semantics; so the attributes: model/vendor/swRev/hwRev must have a value (not "d").
Also IEC 61869-9 table 903 defines a format for the special PhyNam data objects. Tissue #1788 has been raised to clarify if these value should/shall be in SCL. For now we added the "non-empty" value checks in sSvp23. Later on when the tissue is resolved the test procedure can be updated again.
Compare attached file 210827.
Updated by Bruce Muschlitz about 3 years ago
- Status changed from In Progress to Closed
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)