Improvement #3100
IEC61850.Tissue #1754 Event driven schedules - Type of InSyn missing
0%
Include in edition 3 - not very urgent
IEC 61850-7-4
Description
Part 7-4, page 169, clause 6.6.9, table 70:
The type of the external trigger InSyn in Table 70 is not defined.
Note: InSyn is also used for Statistical LN … but the definition there is not applicable for scheduling.
“F.3.2.3 External synchronization” defines BOOLEAN … and the behavior only for statistical LN … NOT for FSCH!
Proposal descriptions
Define the Type of external trigger.
Replace the current text:
“Object reference of the external trigger if the
schedule is triggered by an event.”
with
“Object reference of the external trigger to start the schedule
if the schedule is triggered by an event.
The Type of the external trigger Data Attribute
shall be BOOLEAN.”
Note: This Data Attribute may be located in the same IED (local issue how the event is communicated) or in another IED (needs GOOSE or Report to communicate the event from one IED to another IED).
Alternatively a new clause like F.3.2.3 External synchronization could be added in K.2.4
Related issues
Updated by Carlos Rodriguez del Castillo about 3 years ago
- Due date set to 02/10/2022
- ID set to 2
- Source set to TissueDB
- TF Unique ID set to 2 # TissueDB
- TF Unique ID set
- Due date updated
Updated by Carlos Rodriguez del Castillo about 3 years ago
- Status changed from New to Resolved
- Short Proposal set to Include in edition 3 - not very urgent
- Standard(s) set to IEC 61850-7-4
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from No to Yes
Updated by Carlos Rodriguez del Castillo over 1 year ago
- Discuss in Upcoming Meeting changed from Yes to No
Updated by Vladan Cvejic about 1 year ago
- Copied to WG10 Future Work #6604: IEC61850.Tissue #1754 Event driven schedules - Type of InSyn missing added