Issues #3079
sSvp13 Quality bit invalid - change to Conditional
Status:
Closed
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
9-2
Triggering Tissue:
Final Decision:
sSvp13 now Conditional
Initial Test Document:
Updated Test Document:
Test Case ID:
sSvp13
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
test case sSvp13 is related to backwards configuration which may have current/voltage sampled values that are not measured and as such shall have quality=invalid. This is specified in the PIXIT Svp9. The test case should be changed from Mandatory to Conditional.
Files
Updated by Richard Schimmel almost 4 years ago
- File Solution to redmine_3079_sSvp13.docx Solution to redmine_3079_sSvp13.docx added
- Status changed from New to In Progress
Updated by Richard Schimmel almost 4 years ago
- Status changed from In Progress to Resolved
- Final Decision set to sSvp13 now Conditional
TPWG agreement resolved
Updated by Richard Schimmel over 3 years ago
- Status changed from Resolved to Closed
- Initial Test Document changed from Amd1 to Ed2Amd1 TP1.0
- Updated Test Document set to Ed2Amd1 TP1.1
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)