CIM Issues #6299
Updated by Todd Viegut about 1 month ago
Three new enum literals were added to the existing *LimitKind* enumeration in the *OperationalLimits* package:
* normal – The rating as defined by the equipment owner that specifies the level of electrical loading, usually expressed in megawatts (MW) or other appropriate units that a system, facility, or element can support or withstand through the daily demand cycles without loss of equipment life.
* emergency – The rating as defined by the equipment owner that specifics the level of electrical loading or output, usually expressed in megawatts (MW) or Mvar, or other appropriate units, that a system, facility, or element can support, procedure, or withstand for a finite period. The rating assumes acceptable loss of equipment life or other physical or safety limitations for the equipment involved.
* loadShedding - Would be considered another type of Emergency rating that typically has a shorter duration
The 452 Core profile was also updated to include the three new literals and the <<European>> stereotype was removed on the enumeration.