CIM Issues #6299
Updated by Todd Viegut about 1 month ago
Please add the following new enums to the LimitKind enumeration used by OperationalLimitType.kind;
Pulled from NERC documentation is the following definitions:
Normal Rating – The rating as defined by the equipment owner that specifies the level of electrical
loading, usually expressed in megawatts (MW) or other appropriate units that a system, facility, or
element can support or withstand through the daily demand cycles without loss of equipment life.
Emergency Rating – The rating as defined by the equipment owner that specifics the level of electrical
loading or output, usually expressed in megawatts (MW) or Mvar, or other appropriate units, that a
system, facility, or element can support, procedure, or withstand for a finite period. The rating assumes
acceptable loss of equipment life or other physical or safety limitations for the equipment involved.
Load Shed Rating - Would be considered another type of Emergency rating that typically has a shorter duration