Please add the following new enums to the LimitKind enumeration used by OperationalLimitType.kind; 
 Pulled from NERC documentation is the following definitions: 

 Normal Rating – The rating as defined by the equipment owner that specifies the level of electrical 
 loading, usually expressed in megawatts (MW) or other appropriate units that a system, facility, or 
 element can support or withstand through the daily demand cycles without loss of equipment life. 

 Emergency Rating – The rating as defined by the equipment owner that specifics the level of electrical 
 loading or output, usually expressed in megawatts (MW) or Mvar, or other appropriate units, that a 
 system, facility, or element can support, procedure, or withstand for a finite period. The rating assumes 
 acceptable loss of equipment life or other physical or safety limitations for the equipment involved. 

 Load Shed Rating - Would be considered another type of Emergency rating that typically has a shorter duration