CIM Issues #7117
Relax cardinality requirement of VoltageCompensatorDynamics model for every instance of an ExcitationSystemDynamics model.
IEC61970-457
Description
Change the cardinality from 1..1 to 0..1 for the VoltageCompensatorDynamics association with the ExcitationSystemDynamics. Generator Dynamic models exist with Excitation models that do not require a VoltageCompensator model. All other types of models associated with the ExcitationSystemDynamics are optional with a cardinality of 0..1. VoltageCompensatorDynamics is the only class that has a required 1..1 cardinality.
In fact, even the Examples shown in the Dynamics package contradict this required association (each diagram shows an example of an Exciter dynamic model that does not have a Voltage Compensator model).
Files
Proposed Solution
Change the cardinality from 1..1 to 0..1 for the VoltageCompensatorDynamics association with the ExcitationSystemDynamics.