Issues #7097
Step number error in expected result of sGos6b in Rev1.3 test procedure
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
In Rev1.3 test procedure, a new Step 5 was added to the "test description" of sGos6a (increasing the number of steps).
However, this change was not considered in "Expected result" of sGos6b.
The mapping of "Expected result" to "test description" is incorrect.
The "Expected result" of sGos6b should start from Step 7.
Updated by Richard Schimmel 1 day ago
Agree numbering does not match. Expected 6->7, 7->8, 8->9, 10->11, 11->12, 12->13, keep 14.
Updated by IEC 61850 TPWG about 10 hours ago
- Status changed from New to Resolved
- Assignee set to Richard Schimmel
Agreed. Richard to correct numbering.