Project

General

Profile

CIM Issues #6773

DC device containment rules need to be updated

Added by Todd Viegut 8 months ago. Updated 3 months ago.

Status:
In Progress
Priority:
Normal
Author/Contact Info:
Chavdar Ivanov
Base Release:
Solution to be Applied To:
Solution Version:
CIM18
Solution Applied By:
Completion Date:
CIM Keywords:
61970-DC
Breaking Change:
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):

IEC61970-301, IEC61970-452

Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
Origination ID:
Originally Assigned To:

Description

DCNode does not have a 452 constraint and all other DCConductingEquipment are contained in a DCConverterUnit which will be insufficient if we have DC grid (DC substations, DC switches, etc.)

As part of this effort we need to evaluate the <<NC>> extensions that include DCSubstation, DCSubstationPole, DCSubstationBipole, etc. for inclusion in CIM18. This would require some rework/updates on equipment containment.


Proposed Solution

Proposal is to migrate the <<NC>> extensions mentioned in the description of this issue into CIM18 normatively. Also to updated our containment clauses within the 301 and the 452, etc.


Decision

19-Sep-2024 Joint TF Hybrid Meetings - Minneapolis:

Action Item: The constraints need to be checked/verified.

#1

Updated by Chavdar Ivanov 4 months ago

  • Status changed from New to Open
#2

Updated by Todd Viegut 3 months ago

  • Status changed from Open to In Progress
  • Decision updated (diff)

Also available in: Atom PDF