T1679 GoEna behavior at startup

Added by Bruce Muschlitz about 3 years ago. Updated almost 2 years ago.

Status:
Closed
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-2
Final Decision:
See attachment 20210504
Updated Test Document:
Test Case ID:
sGop3
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

Based upon TISSUE 1679, change expected startup value of GoEna from indeterminate to "true when GOOSE is well-configured:"
(i.e. there is an implicit SetGoCBValues(GoEna,true) at startup but without any tracking trigger)


Files

TestProcedure_sGop3.docx TestProcedure_sGop3.docx 13.7 KB Bruce Muschlitz, 04/20/2021 03:16 PM
TestProcedure_sGop3_20210504.docx TestProcedure_sGop3_20210504.docx 13.8 KB Bruce Muschlitz, 05/04/2021 08:41 AM
#1

Updated by Richard Schimmel almost 3 years ago

  • Status changed from New to In Progress
#2

Updated by Bruce Muschlitz almost 3 years ago

Added note that TICS needs update

#3

Updated by Richard Schimmel almost 3 years ago

  • Subject changed from GoEna behavior at startup to T1679 GoEna behavior at startup
#4

Updated by Bruce Muschlitz almost 2 years ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to Server Ed2.1 TP1.2
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)