Project

General

Profile

Issues #6565

Added more precise qualifications to TmSrcTyp - 1883

Added by IEC 61850 TPWG 6 months ago. Updated 5 months ago.

Status:
Rejected
Priority:
Normal
Due date:
11/14/2023 (about 6 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-4
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sTm5, sTmP5
Closed Reason:
No Action Taken
Triggering Tissue 2:
Triggering Tissue 3:
#1

Updated by IEC 61850 TPWG 6 months ago

  • Due date changed from 11/07/2023 to 11/14/2023
  • Status changed from New to In Progress
#2

Updated by IEC 61850 TPWG 6 months ago

  • Assignee set to Richard Schimmel
#3

Updated by Richard Schimmel 5 months ago

  • Subject changed from Added more precise qualifications to TmSrcTyp - 1883 to Added more precise qualifications to TmSrcTyp - 1883
  • Initial Test Document set to Ed2.1 TP1.2
  • Test Case ID set to sTm5, sTmP5

sTm5 validates LTMS.TmSrcTyp=SNTP, sTmP5 validates LTMS.TmSrcTyp=PTP. When the clocksource is unavailable the applicable TmChStX changes from True to False. Is this sufficient?

#4

Updated by IEC 61850 TPWG 5 months ago

  • Closed Reason No Action Taken added
  • Closed Reason deleted (--Not Set---)

No change in test procedure.

#5

Updated by IEC 61850 TPWG 5 months ago

  • Status changed from In Progress to Rejected

Also available in: Atom PDF