Issues #6565
Added more precise qualifications to TmSrcTyp - 1883
Due date:
11/14/2023 (about 13 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
7-4
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sTm5, sTmP5
Closed Reason:
No Action Taken
Triggering Tissue 2:
Triggering Tissue 3:
Updated by IEC 61850 TPWG about 1 year ago
- Due date changed from 11/07/2023 to 11/14/2023
- Status changed from New to In Progress
Updated by Richard Schimmel about 1 year ago
- Subject changed from Added more precise qualifications to TmSrcTyp - 1883 to Added more precise qualifications to TmSrcTyp - 1883
- Initial Test Document set to Ed2.1 TP1.2
- Test Case ID set to sTm5, sTmP5
sTm5 validates LTMS.TmSrcTyp=SNTP, sTmP5 validates LTMS.TmSrcTyp=PTP. When the clocksource is unavailable the applicable TmChStX changes from True to False. Is this sufficient?
Updated by IEC 61850 TPWG about 1 year ago
- Closed Reason No Action Taken added
- Closed Reason deleted (
--Not Set---)
No change in test procedure.