Project

General

Profile

CIM Issues #6461

302,457 issue PowerFlowSettings missing 3 attributes

Added by Chavdar Ivanov about 1 year ago. Updated about 1 year ago.

Status:
Closed
Priority:
Normal
Author/Contact Info:
Chavdar Ivanov
Base Release:
18v03
Solution to be Applied To:
18v05
Solution Version:
CIM18v05
Solution Applied By:
Chavdar Ivanov
Completion Date:
07/02/2023
CIM Keywords:
61970-Dynamics
Breaking Change:
No
Breaking Change Description:
CIM Impacted Groups:
WG13
Requestor:
Standard(s):
Version:
Clause:
Sub-Clause:
Paragraph:
Table:
Originally Closed in Version:
Origination Date:
05/17/2023
Origination ID:
Originally Assigned To:

Description

PowerFlowSettings class is missing 3 important attributes to complete the basic settings for the power flow
- maxIterationsInnerLoop
- maxIterationsOuterLoop
- loadResponseCharacteristicsEnabled

These were discussed but got forgoten in last iterations


Proposed Solution

Add the following attributes and profile them in 457 as required attributes
- maxIterationsInnerLoop, integer, Description: Maximum iterations of inner loop of the power flow calculation algorithm.
- maxIterationsOuterLoop, integer, Description: Maximum iterations of outer loop of the power flow calculation algorithm. This can refer to the maximum number of iterations when area interchange control is used.
- loadResponseCharacteristicsEnabled, boolean, Description: True means load response characteristics are considered, if present in the model. False, means that even if enabled, the load response characteristics are not taken into account by the power flow calculation algorithm.


Decision

Add as proposed. It was a miss by the project work. The gap was identified recently


Release Notes

The following attributes are added to 302 and 457 as required attributes in simulation settings profile
- maxIterationsInnerLoop, integer, Description: Maximum iterations of the power flow calculation algorithm inner loop.
- maxIterationsOuterLoop, integer, Description: Maximum iterations of the power flow calculation algorithm outer loop. This can refer to the maximum number of iterations when area interchange control is performed as part of an outer loop or when specific control actions are done in the outer loop.
- loadResponseCharacteristicsEnabled, boolean, Description: True means load response characteristics are considered, if present in the model. False, means that even if enabled, the load response characteristics are not taken into account by the power flow calculation algorithm.

Also available in: Atom PDF