Issues #6324
sCnf6 - not all extRef require intAddr not referring to external device
Due date:
05/16/2023 (about 11 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf6
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sCnf6 states: Note: the intAddr should not contain external data.
I agree with this note when ExtRefs are in the ICD file. These are the "later binding" kind of ExtRefs.
When an ICT tool completes a later binding ExtRef from the ICD and exports the IID is it allowed to remove not used later binding ExtRefs? it should keep the intAddr value.
When an SCT/ICT tool adds new ExtRef and exports the IID it is allowed to use intAddr containing external data!
Update the test procedure accordingly
Updated by IEC 61850 TPWG 12 months ago
- Due date set to 05/16/2023
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Richard to review further.
Updated by IEC 61850 TPWG 11 months ago
- Status changed from In Progress to Rejected
Disagree. No change.
SCT is allowed to change extRef.
intAddr are local issue.