Issues #6324
sCnf6 - not all extRef require intAddr not referring to external device
Due date:
05/16/2023 (about 19 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf6
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:
Description
sCnf6 states: Note: the intAddr should not contain external data.
I agree with this note when ExtRefs are in the ICD file. These are the "later binding" kind of ExtRefs.
When an ICT tool completes a later binding ExtRef from the ICD and exports the IID is it allowed to remove not used later binding ExtRefs? it should keep the intAddr value.
When an SCT/ICT tool adds new ExtRef and exports the IID it is allowed to use intAddr containing external data!
Update the test procedure accordingly
Updated by IEC 61850 TPWG over 1 year ago
- Due date set to 05/16/2023
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Richard to review further.
Updated by IEC 61850 TPWG over 1 year ago
- Status changed from In Progress to Rejected
Disagree. No change.
SCT is allowed to change extRef.
intAddr are local issue.