Project

General

Profile

Issues #6324

sCnf6 - not all extRef require intAddr not referring to external device

Added by Richard Schimmel 12 months ago. Updated 11 months ago.

Status:
Rejected
Priority:
Normal
Due date:
05/16/2023 (about 11 months late)
Discuss in Upcoming Meeting:
No
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCnf6
Closed Reason:
--Not Set---
Triggering Tissue 2:
Triggering Tissue 3:

Description

sCnf6 states: Note: the intAddr should not contain external data.

I agree with this note when ExtRefs are in the ICD file. These are the "later binding" kind of ExtRefs.

When an ICT tool completes a later binding ExtRef from the ICD and exports the IID is it allowed to remove not used later binding ExtRefs? it should keep the intAddr value.

When an SCT/ICT tool adds new ExtRef and exports the IID it is allowed to use intAddr containing external data!

Update the test procedure accordingly

#1

Updated by IEC 61850 TPWG 12 months ago

  • Due date set to 05/16/2023
  • Status changed from New to In Progress
  • Assignee set to Richard Schimmel

Richard to review further.

#2

Updated by IEC 61850 TPWG 11 months ago

  • Status changed from In Progress to Rejected

Disagree. No change.

SCT is allowed to change extRef.

intAddr are local issue.

Also available in: Atom PDF