Project

General

Profile

Bug #611

Need a new DO (ENUM) to identify the protocol used for the SCADA exchange, in LN ITCI

Added by Carlos Rodriguez del Castillo almost 4 years ago. Updated about 1 year ago.

Status:
In Progress
Priority:
Normal
Assignee:
-
Category:
-
Start date:
10/07/2020
Due date:
08/16/2021 (over 3 years late)
% Done:

0%

Estimated time:
ID:
5
Source:
RTE
TF Unique ID:
5 # RTE
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
No
Short Proposal:

Check 80-6.

Standard(s):

IEC 61850-7-4 / IEC 61850-80-6

Needs More Information:
Yes
Assigned TF:

Description

This ENUM will allow to identify the type of the distant center (104, IEC61850), in case several centers are connected to the substation.
Helpful for maintenance and exploitation of the system.


Proposal descriptions

After reviewing, RTE does not need a DO for that purpose. RTE will take a look on 80-6 to check if it fits their needs.

#1

Updated by Carlos Rodriguez del Castillo almost 4 years ago

  • Status changed from New to In Progress
  • Start date changed from 02/15/2021 to 10/08/2020
  • Short Proposal set to It might be interesting to have a DO describing de protocol. We should create the use case.
  • WG10 Proposal set to To be addressed in Ed.3
  • Discuss in Upcoming Meeting changed from No to Yes
#2

Updated by Carlos Rodriguez del Castillo almost 4 years ago

  • Start date changed from 10/08/2020 to 10/07/2020
#3

Updated by Carlos Rodriguez del Castillo almost 4 years ago

  • Due date set to 08/16/2021
  • Status changed from In Progress to Triage
  • To discuss in WG10 set to No
#4

Updated by Carlos Rodriguez del Castillo almost 4 years ago

2021-03-02: There is a proposal for 101 and 104 to use subnetwork type to identify the protocol in 80-6 (Andreas Ostermeier). But RTE request is to create a DO in order to interchange this information between devices. RTE will check and provide the use case.
You can define two different access point to the same physical ethernet interface, having two subnetworks with different subnetwork type. This is for the example of having IEC 61850 and IEC 60870-5-104 running on the same ethernet interface.

#5

Updated by Carlos Rodriguez del Castillo over 3 years ago

  • Subject changed from Need a new DO (ENUM) to identify the protocol used for the SCADA exchange, in LN ITCI or LCCH to Need a new DO (ENUM) to identify the protocol used for the SCADA exchange, in LN ITCI
  • Status changed from Triage to In Progress
  • Short Proposal changed from It might be interesting to have a DO describing de protocol. We should create the use case. to Check 80-6.
  • Standard(s) changed from IEC 61850-7-4 to IEC 61850-7-4 / IEC 61850-80-6
  • WG10 Proposal deleted (To be addressed in Ed.3)
  • Discuss in Upcoming Meeting changed from Yes to No
  • Proposal descriptions updated (diff)

2021-05-11: RTE will have a look at the draft of TR 80-6, which propose to use sub network type

#6

Updated by Vladan Cvejic about 1 year ago

  • Discuss in Upcoming Meeting changed from No to Yes
  • Needs More Information set to Yes
#7

Updated by Vladan Cvejic about 1 year ago

  • Discuss in Upcoming Meeting changed from Yes to No

Also available in: Atom PDF