Description

IEC TS 62361-102 Recommendation R12:

Revise the IEC 61970 SCADA package as proposed in Figure 16. (see attachment)
The major change is to make a RemoteUnit a specialization of MeasurementValueSource and to separate the semantics of scan/update interval versus SCADA limit information.
This change allows the merging of the Measurement and SCADA models and allows RemoteUnits and IEDs to be directly associated with the MeasurementValues that are being sourced.


Files


Decision

16-Sep-2024 Joint TF Hybrid Meeting - Minneapolis:

Reviewed together.

Action Item: Alex and Tom to check the issues and see what are low hanging fruits that can be easily fixed and which of the items will be followed up in the new TF subteam on the topic and which issues are to be assigned to CIM19