Issues #5959
sSvp3 remove random and allow synSourceID=TRUE for backwards compatible config
Description
Step 1 shall not use the random but the "same configuration as sSvp1" (compare for example sSvp2)
Second issue: is the backward configuration with synchSourceID=True considered as a backward compatible config? The 9-2LE does not have synSourceID. But newer devices may use backward configuration with PTP and synchSourceID. Clarify for step 6 which steps shall be repeated or even better create step 6-7-8-9:
Proposal:
1. Configure the DUT with the same configuration as sSvp1
2. Generate current and/or voltage signals
3. if PTP is supported configure synchSourceId to TRUE and capture SV messages for at least 1 second
4. if PTP is supported configure synchSourceId to FALSE and capture SV messages for at least 1 second
5. Configure the DUT with the lowest rate backwards compatible configuration
6. Generate current and/or voltage signals
7. if PTP is supported configure synchSourceId to TRUE and capture SV messages for at least 1 second
8. if PTP is supported configure synchSourceId to FALSE and capture SV messages for at least 1 second
Updated by IEC 61850 TPWG about 2 years ago
- Due date set to 09/20/2022
- Status changed from New to In Progress
- Assignee set to Richard Schimmel
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3