Issues #5907
sCtl26 - Cancel a direct control object
Due date:
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl26
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:
Description
The test condition for sCtl26 is: command-already-in-execution and operateTimeout>0. However the (direct) control object also should have a Cancel structure.
Proposal change condition into: command-already-in-execution, operateTimeout and Cancel
Updated by IEC 61850 TPWG over 2 years ago
- Status changed from New to Resolved
- Assignee set to Richard Schimmel
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)
Add condition as described.
Updated by Richard Schimmel 9 months ago
- Status changed from Resolved to Closed
- Updated Test Document set to TP1.3