sCtl26 - Cancel a direct control object

Added by Richard Schimmel over 2 years ago. Updated 9 months ago.

Status:
Closed
Priority:
Normal
Due date:
Discuss in Upcoming Meeting:
Yes
Clause Reference:
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
sCtl26
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

The test condition for sCtl26 is: command-already-in-execution and operateTimeout>0. However the (direct) control object also should have a Cancel structure.
Proposal change condition into: command-already-in-execution, operateTimeout and Cancel

#1

Updated by IEC 61850 TPWG over 2 years ago

  • Status changed from New to Resolved
  • Assignee set to Richard Schimmel
  • Closed Reason Test Procedure Update added
  • Closed Reason deleted (--Not Set---)

Add condition as described.

#2

Updated by Richard Schimmel 9 months ago

  • Status changed from Resolved to Closed
  • Updated Test Document set to TP1.3