Support #560
Busbar protection: Simplified logic
Status:
Closed
Priority:
Normal
Assignee:
-
Category:
Out of Scope
Start date:
Due date:
% Done:
0%
Estimated time:
ID:
32
Source:
ENTSO-E
TF Unique ID:
32 # ENTSO-E
WG10 Proposal:
Estimated Completion:
Discuss in Upcoming Meeting:
No
To discuss in WG10:
Short Proposal:
•The PDIR covers the simplified busbar protection based on directional overcurrent•The ramelot (specific Elia application) is not covered by the standard but you could through eningeering derive if the trip comes from the ramelot (by using a specific stage of the overcurrent protection, that can be blocked by feeder overcurrent operates)PDIR covers simplified logic protection and ramelot
Standard(s):
IEC 61850-7-4
Needs More Information:
Assigned TF:
Description
Busbar protection: Simplified logic
(used for ex as a combination of the start of backward distance protection zones or combining overcurrent start en directional overcurrent blocking)