CIM Issues #5313
Better description for governorSCD
Description
The current description is: Governor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
We use the term “Governor Speed Changer Droop” One could read this as the droop if the speed changer of the governor. Is this what we want? Could we just say “Governor speed droop”
Then the rest defines “the change in generator power output divided by the change in frequency” which is deltaP/delta_f. I guess this maybe also works, but I see it mostly defined change of frequency divided by change of change of P.
Then we have – normalized, percent, negated,… Maybe we can just write as equation.
The description becomes cumbersome to describe the behavior, could be improved by incorporating an equation.
Decision
19-Sep-2024 Joint TF Hybrid Meetings - Minneapolis:
Reviewed. Below are identified AIs:
AI [Chavdar]: Create a proposal that takes into account the provided documents (linked in an earlier comment). % may vary. Note that we'll also need to have the typical pattern and include the normal* attribute as well.
Updated by Chavdar Ivanov almost 3 years ago
Example from Marcos Olmos
Generator PR: 100MW, fR=50Hz
Kr=3 MW/Hz
governorSCD = ( delta P/PR) / (delta f/fR) = (3MW/100MW) / (1Hz/50Hz) = 150%
Links from Chavdar
Microsoft Word - Item 12i - Memo from Etter to Board re Compensation 07Dec2016.docx (nerc.com): https://www.nerc.com/pa/Stand/BAL001TRE1/BAL-001-TRE-1%20Redline.pdf
Microsoft Word - Wsccgov1.doc (wecc.org): https://www.wecc.org/Reliability/Governor%20Tutorial.pdf
Updated by Yang Feng over 2 years ago
WG13 has agreed to include the equation to replace the context, the proposed context will be sent to WG13 for review later.