sCnf125 smvOpts sampleSynchronized=true or absent, dataSet=false or absent

Added by Richard Schimmel over 2 years ago. Updated about 2 years ago.

Status:
Closed
Priority:
Normal
Assignee:
-
Due date:
Discuss in Upcoming Meeting:
No
Clause Reference:
IEC 61850-6 Table 31
61850 Standard:
Triggering Tissue:
Final Decision:
Initial Test Document:
Updated Test Document:
Test Case ID:
Closed Reason:
Test Procedure Update
Triggering Tissue 2:
Triggering Tissue 3:

Description

IEC 61850-6 and IEC 61869-9 are not consistent related to smvOpt. Part 6 table 31 states smvOpts: dataRef and sampleSynchronized are deprecated but are kept in SCL for backwards compatible reasons. As such we have to update sCnf125:

OLD:
Verify the SmvOpts (clause 6.903.11)
- SmvOpt: sampleSynchronized="true" refreshTime="false" sampleRate="false" dataSet="false" security="false"

NEW:
Verify the SmvOpts (clause 6.903.11 and IEC 61850-6 Table 31)
- SmvOpt: sampleSynchronized="true" or absent; refreshTime="false"; sampleRate="false"; dataSet="false" or absent; security="false"