Issues #5292
sCnf125 smvOpts sampleSynchronized=true or absent, dataSet=false or absent
Description
IEC 61850-6 and IEC 61869-9 are not consistent related to smvOpt. Part 6 table 31 states smvOpts: dataRef and sampleSynchronized are deprecated but are kept in SCL for backwards compatible reasons. As such we have to update sCnf125:
OLD:
Verify the SmvOpts (clause 6.903.11)
- SmvOpt: sampleSynchronized="true" refreshTime="false" sampleRate="false" dataSet="false" security="false"
NEW:
Verify the SmvOpts (clause 6.903.11 and IEC 61850-6 Table 31)
- SmvOpt: sampleSynchronized="true" or absent; refreshTime="false"; sampleRate="false"; dataSet="false" or absent; security="false"
Updated by Bruce Muschlitz about 3 years ago
- Status changed from In Progress to Resolved
Per TPWG meeting 2022-03-22, this is obvious typographical error to be fixed in Ed2.1 Server TP 1.2
Updated by Richard Schimmel about 3 years ago
Also smpMod=SmpPerPeriod or absent. Note that SmpMod shall be s mpMod.
Updated by Richard Schimmel almost 3 years ago
Part 6 A.4 specifies default values for all SmvOpts options:
Verify the SmvOpts (clause 6.903.11 and IEC 61850-6 Table 31) and part 6 A.4
- SmvOpt:
sampleSynchronized="true" or absent;
refreshTime="false" or absent;
sampleRate="false" or absent;
dataSet="false" or absent;
security="false" or absent
Updated by Bruce Muschlitz almost 3 years ago
- Status changed from Resolved to Closed
- Updated Test Document set to Server Ed2.1 TP1.2
- Closed Reason Test Procedure Update added
- Closed Reason deleted (
--Not Set---)